8.2.8
Technical data
M12342-1 v21
Table 219: OC4PTOC (51/67) technical data
Function
Range or value
Accuracy
Trip current, step 1-4
(5-2500)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Reset ratio
> 95% at (50–2500)% of
lBase
-
Minimum operate current, step 1-4
(1-10000)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Relay characteristic angle (RCA)
(40.0–65.0) degrees
±
2.0 degrees
Relay operating angle (ROA)
(40.0–89.0) degrees
±
2.0 degrees
Second harmonic blocking
(5–100)% of fundamental
±
2.0% of I
n
Independent time delay at 0 to 2 x I
set
, step
1-4
(0.000-60.000) s
±
0.2% or
±
35 ms whichever is greater
Minimum trip time for inverse curves , step
1-4
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Inverse time characteristics, see
table
, table
and table
16 curve types
See table
, table
and table
Trip time, pickup non-directional at 0 to 2 x
I
set
Min. = 15 ms
-
Max. = 30 ms
Reset time, pickup non-directional at 2 x
I
set
to 0
Min. = 15 ms
-
Max. = 30 ms
Operate time, start non-directional at 0 to
10 x I
set
Min. = 5 ms
Max. = 20 ms
-
Reset time, start non-directional at 10 x I
set
to 0
Min. = 20 ms
Max. = 35 ms
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Operate frequency, directional overcurrent
38-83 Hz
-
Operate frequency, non-directional
overcurrent
10-90 Hz
-
8.3
Instantaneous residual overcurrent protection EFPIOC
(50N)
IP14508-1 v3
1MRK 502 066-UUS B
Section 8
Current protection
467
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...