Function of quantity
Static binary output trip
220 V/0.2 A
250 V/0.15 A
Operating time
< 1 ms
< 1 ms
Table 1021: SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Function of quantity
Trip and signal relays
Max system voltage
250 V AC/DC
Min load voltage
24VDC
Number of outputs
6
Test voltage across open contact, 1 min
1000 V rms
Current carrying capacity:
Continuous
8 A
1.0 s
10 A
Max operations with load
1000
Max operations with no load
10000
Making capacity at capacitive load with the maximum
capacitance of 0.2 μF:
0.2 s
30 A
1.0 s
10 A
Breaking capacity for DC with L/R ≤ 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Operating time
< 6 ms
Maximum 72 outputs may be activated simultaneously with influencing factors
within nominal range. After 6 ms an additional 24 outputs may be activated. The
activation time for the 96 outputs must not exceed 200 ms. 48 outputs can be
activated during 1 s. Continued activation is possible with respect to current
consumption but after 5 minutes the temperature rise will adversely affect the
hardware life. Maximum two relays per BOM/IOM/SOM should be activated
continuously due to power dissipation.
The stated operate time for functions include the operating time for the binary
inputs and outputs.
Section 22
1MRK 502 066-UUS B
IED hardware
1306
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...