Figure
is valid for phase-to-ground. During a three-phase fault, or load, when the quadrilateral
phase-to-phase characteristic is subject to enlargement and rotation the operate area is
transformed according to figure
. Notice in particular what happens with the resistive blinders
of the "phase selection" "quadrilateral" zone. Due to the 30-degree rotation, the angle of the
blinder in quadrant one is now 90 degrees instead of the original 60 degrees. The blinder that is
nominally located to quadrant four will at the same time tilt outwards and increase the resistive
reach around the R-axis. Consequently, it will be more or less necessary to use the load
encroachment characteristic in order to secure a margin to the load impedance.
R
X
Distance measuring zone
Phase selection
”Quadrilateral” zone
IEC09000049-1-en.vsd
)
/
(
phase
W
)
/
(
phase
W
IEC09000049 V1 EN-US
Figure 89: Operating characteristic for FDPSPDIS (21) in forward direction for three-phase
fault, ohm/phase domain
The result from rotation of the load characteristic at a fault between two phases is presented in
fig
. Since the load characteristic is based on the same measurement as the quadrilateral
characteristic, it will rotate with the quadrilateral characteristic clockwise by 30 degrees when
subject to a pure phase-to-phase fault. At the same time the characteristic will "shrink", divided by
2/√3, from the full
RLdFw and RLdRv reach, which is valid at load or three-phase fault.
Section 7
1MRK 502 066-UUS B
Impedance protection
208
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...