15.15.6.1
Operation accuracy
GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3
The accuracy of TEIGAPC depends on essentially three factors
•
function cycle time
•
the pulse length
•
the number of pulses, that is, the number of rising and falling flank pairs
In principle, a shorter function cycle time, longer integrated time length or more pulses may lead
to reduced accuracy.
15.15.6.2
Memory storage
GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3
The value of the integrated elapsed time is retained in a non-volatile memory.
15.15.7
Technical data
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 710: TEIGAPC Technical data
Function
Cycle time (ms)
Range or value
Accuracy
Elapsed time integration
3
0 ~ 999999.9 s
±0.2% or ±20 ms whichever
is greater
8
0 ~ 999999.9 s
±0.2% or ±100 ms whichever
is greater
100
0 ~ 999999.9 s
±0.2% or ±250 ms whichever
is greater
Table 711: Number of TEIGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TEIGAPC
4
4
4
15.16
Comparator for integer inputs - INTCOMP
15.16.1
Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values
INTCOMP
Int<=>
15.16.2
Functionality
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
The function gives the possibility to monitor the level of integer values in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.
Section 15
1MRK 502 066-UUS B
Logic
1002
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...