The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the double point values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
18.12
GOOSE function block to receive an integer value
GOOSEINTRCV
18.12.1
Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive an
integer value
GOOSEINTRCV
-
-
18.12.2
Functionality
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v2
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via GOOSE.
18.12.3
Function block
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
IEC10000250-1-en.vsd
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V1 EN-US
Figure 611: GOOSEINTRCV function block
18.12.4
Signals
PID-2529-INPUTSIGNALS v18
Table 913: GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Section 18
1MRK 502 066-UUS B
Station communication
1200
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...