Condition 1 and
Condition 2 ⇒
Fault type
CG
CG
CG
BG
AG
BCG
The sequence phase selector is blocked when ground is not involved or if a three-phase fault is
detected.
Three-phase fault detection
SEMOD153832-174 v4
Unless it has been categorized as a single or two-phase fault, the function classifies it as a three-
phase fault if the following conditions are fulfilled:
|V
1
|
V1Level
and
|I
1
|>
I1LowLevel
or
|I
1
|>
IMaxLoad
where:
V
1
| and |I
1
|
are the positive sequence voltage and current magnitude
V1Level ,
I1LowLevel
are the setting of limits for positive sequence voltage and current
IMaxLoad
is the setting of the maximum load current
The output signal for detection of three-phase fault is only released if not ground fault and phase-
to-phase fault in the main sequence function is detected.
The conditions for not detecting ground fault are the inverse of equation 5 to 10.
The condition for not detecting phase-to-phase faults is determined by three conditions. Each of
them gives condition for not detecting phase-to-phase fault. Those are:
1:
ground fault is detected
or
|3I
0
|> 0.05 ·
IBase
and
|3I
0
|>maxIph ·
INRelPG
2:
phase-to-ground and phase-to-phase faults are not fulfilled
and
maxIph<0.1 ·
IBase
and
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
250
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...