Name
Values (Range)
Unit
Step
Default
Description
FrLowLowLim
0.000 - 100.000
Hz
0.001
45.000
Low Low limit (physical value)
FrLimHyst
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
VGenZeroDb
1 - 100
%VB
1
5
Zero point clamping in % of UBase
IGenZeroDb
1 - 100
%IB
1
5
Zero point clamping in % of IBase
VMagComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at
5% of Vn
VMagComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at
30% of Vn
VMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate voltage at
100% of Vn
IMagComp5
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at
5% of In
IMagComp30
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at
30% of In
IMagComp100
-10.000 - 10.000
%
0.001
0.000
Magnitude factor to calibrate current at
100% of In
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of In
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of In
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of In
PID-3760-SETTINGS v6
Table 734: CMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IA_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation
Disabled
Enabled
-
-
Disabled
Disbled/Enabled operation
IA_Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IA_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
IA_AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IB_RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
IB_AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table continues on next page
1MRK 502 066-UUS B
Section 16
Monitoring
1019
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...