17.2.3
Function block
SEMOD175502-4 v5
ETPMMTR
P*
Q*
STARTACC
STOPACC
RSTACC
RSTDMD
ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
ERRPULSE
EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD
IEC14000019-1-en.vsd
IEC14000019 V1 EN-US
Figure 576: ETPMMTR function block
17.2.4
Signals
PID-3843-INPUTSIGNALS v5
Table 803: ETPMMTR Input signals
Name
Type
Default
Description
P
REAL
0
Measured active power
Q
REAL
0
Measured reactive power
STARTACC
BOOLEAN
0
Start to accumulate energy values
STOPACC
BOOLEAN
0
Stop accumulating energy values
RSTACC
BOOLEAN
0
Reset of accumulated enery reading
RSTDMD
BOOLEAN
0
Reset of maximum demand reading
PID-3843-OUTPUTSIGNALS v5
Table 804: ETPMMTR Output signals
Name
Type
Description
ACCINPRG
BOOLEAN
Accumulation of energy values in progress
EAFPULSE
BOOLEAN
Accumulated forward active energy pulse
EARPULSE
BOOLEAN
Accumulated reverse active energy pulse
ERFPULSE
BOOLEAN
Accumulated forward reactive energy pulse
ERRPULSE
BOOLEAN
Accumulated reverse reactive energy pulse
EAFALM
BOOLEAN
Alarm for active forward energy exceed limit in set interval
EARALM
BOOLEAN
Alarm for active reverse energy exceed limit in set interval
ERFALM
BOOLEAN
Alarm for reactive forward energy exceed limit in set interval
ERRALM
BOOLEAN
Alarm for reactive reverse energy exceed limit in set interval
EAFACC
REAL
Accumulated forward active energy value in Ws
Table continues on next page
Section 17
1MRK 502 066-UUS B
Metering
1106
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...