Figure 157: Simplified offset mho characteristic and vector diagram for phase A-to-ground
fault
Operation occurs if 90°≤β≤270°.
Offset mho
GUID-B1EF3931-7B86-4C7B-BCEA-3034482BA240 v1
The condition for operation of offset mho at phase-to-earth fault is that the angle β between the
two compensated voltages is equal to or greater than 90°, see figure
. The angle will be 90° for
fault location on the boundary of the circle.
β =
−
+
⋅
⋅
(
)
−
− −
+
⋅
)
⋅
{
arg
(
)
(
]
V
I
I
K
Z
V
I
I
K
Z
A
A
N
set
A
A
N
RVset
3 0
1
3 0
1
arg
}}
ANSIEQUATION15022 V1 EN-US
(Equation 92)
where
Z
RVset
1
is the complex positive sequence impedance of the line in Ω/
phase for phase-to-ground fault opposite to zone direction and
is defined as,
1MRK 502 066-UUS B
Section 7
Impedance protection
315
Technical manual