en05000089_ansi.vsd
FutureUse
ACK_F_B
ANY_ACK
VALID_TX
RE_RQ_B
V _RE_RQ
BAY_VAL
BAY_RES
EXCH_IN
INT
BIN
BIN
INT
EXCH_OUT
BAY_ACK
BIN……..Binary
INT……..Integer
AND
OR
OR
AND
AND
OR
OR
OR
ANSI05000089 V1 EN-US
Figure 459: Logic diagram for RESIN
Figure
describes the principle of the data exchange between all RESIN modules in the current
bay. There is one RESIN function block per "other bay" used in the reservation mechanism. The
output signal EXCH_OUT in the last RESIN functions are connected to the module bay reserve
(QCRSV) that handles the reservation function in the own bay.
1MRK 502 066-UUS B
Section 14
Control
867
Technical manual