(1
)
Old
Calculated
X
k X
k X
= ×
+ -
×
EQUATION1407 V1 EN-US
(Equation 227)
where:
X
is a new measured value (that is P, Q, S, V, I or PF) to be given out from the function
X
Old
is the measured value given from the measurement function in previous execution cycle
X
Calculated
is the new calculated value in the present execution cycle
k
is settable parameter by the end user which influence the filter properties
Default value for parameter
k is 0.00. With this value the new calculated value is immediately given
out without any filtering (that is, without any additional delay). When
k is set to value bigger than
0, the filtering is enabled. Appropriate value of
k shall be determined separately for every
application. Some typical value for
k =0.14.
Zero point clamping
SEMOD54417-250 v5
In order to avoid erroneous measurements when either current or voltage signal is not present, it
is possible for the end user to set the magnitude
IGenZeroDb level for current and voltage
measurement
VGenZeroDb is forced to zero. When either current or voltage measurement is
forced to zero automatically the measured values for power (P, Q and S) and power factor are
forced to zero as well. Since the measurement supervision functionality, included in CVMMXN, is
using these values the zero clamping will influence the subsequent supervision (observe the
possibility to do zero point clamping within measurement supervision, see section
).
Compensation facility
SEMOD54417-253 v5
In order to compensate for small magnitude and angular errors in the complete measurement
chain (CT error, VT error, IED input transformer errors and so on.) it is possible to perform on site
calibration of the power measurement. This is achieved by setting the complex constant which is
then internally used within the function to multiply the calculated complex apparent power S. This
constant is set as magnitude (setting parameter
PowMagFact, default value 1.000) and angle
(setting parameter
PowAngComp, default value 0.0 degrees). Default values for these two
parameters are done in such way that they do not influence internally calculated value (complex
constant has default value 1). In this way calibration, for specific operating range (for example,
around rated power) can be done at site. However, to perform this calibration it is necessary to
have an external power meter with high accuracy class available.
Directionality
SEMOD54417-256 v6
If CT grounding parameter is set as described in section
, active and reactive
power will be measured always towards the protected object. This is shown in the following
figure
.
Section 16
1MRK 502 066-UUS B
Monitoring
1038
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...