15.14.1
Identification
GUID-C565D235-A935-4405-839D-AAF98E6CB85F v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse integrator
TIGAPC
15.14.2
Functionality
GUID-FF3CBB22-0089-4BA0-BFE3-FD0E5BA96490 v2
The integrator function TIGAPC integrates input pulses and compares the integrated time with a
settable time delay to operate. Moreover, the time delay to reset the output is settable in this
function.
15.14.3
Function block
GUID-045C2E7A-B8B9-479D-8BAF-055E89E5270A v3
TIGAPC
IN
OUT
ANSI14000062-1-en.vsd
ANSI14000062 V1 EN-US
Figure 518: TIGAPC function block
15.14.4
Signals
PID-3497-INPUTSIGNALS v7
Table 702: TIGAPC Input signals
Name
Type
Default
Description
IN
BOOLEAN
0
Input to integrator
PID-3497-OUTPUTSIGNALS v7
Table 703: TIGAPC Output signals
Name
Type
Description
OUT
BOOLEAN
Output from integrator
15.14.5
Settings
PID-3497-SETTINGS v7
Table 704: TIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tDelay
0.000 - 600.000
s
0.001
1.000
Time delay to operate
tReset
0.000 - 600.000
s
0.001
1.000
Time delay to reset
Section 15
1MRK 502 066-UUS B
Logic
996
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...