![ABB Relion 670 series Technical Manual Download Page 917](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_3045226917.webp)
14.6.2
Functionality
SEMOD158756-5 v7
The Selector mini switch VSGAPC function block is a multipurpose function used for a variety of
applications, as a general purpose switch.
VSGAPC can be controlled from the menu or from a symbol on the single line diagram (SLD) on the
local HMI.
14.6.3
Function block
SEMOD158768-4 v3
VSGAPC
BLOCK
PSTO
IPOS1
IPOS2
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
IEC14000066-1-en.vsd
IEC14000066 V1 EN-US
Figure 476: VSGAPC function block
14.6.4
Signals
PID-3829-INPUTSIGNALS v2
Table 549: VSGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PSTO
INTEGER
0
Operator place selection
IPOS1
BOOLEAN
0
Position 1 indicating input
IPOS2
BOOLEAN
0
Position 2 indicating input
PID-3829-OUTPUTSIGNALS v2
Table 550: VSGAPC Output signals
Name
Type
Description
BLOCKED
BOOLEAN
The function is active but the functionality is blocked
POSITION
INTEGER
Position indication, integer
POS1
BOOLEAN
Position 1 indication, logical signal
POS2
BOOLEAN
Position 2 indication, logical signal
CMDPOS12
BOOLEAN
Execute command from position 1 to position 2
CMDPOS21
BOOLEAN
Execute command from position 2 to position 1
1MRK 502 066-UUS B
Section 14
Control
911
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...