![ABB Relion 670 series Technical Manual Download Page 86](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_3045226086.webp)
Description
Value
Voltage inputs **)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
Table 29: TRM - Energizing quantities, rated values and limits for measuring transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1A
5 A
Operating range
(0-1.8) × I
r
(0-1.6) × I
r
Thermal withstand
80 × I
r
for 1 s
25 × I
r
for 10 s
10 × I
r
for 1 min
1.8 × I
r
for 30 min
1.1 × I
r
continuously
65 × I
r
for 1 s
20 × I
r
for 10 s
8 × I
r
for 1 min
1.6 × I
r
for 30 min
1.1 × I
r
continuously
Burden
< 200 mVA at I
r
< 350 mVA at I
r
Voltage inputs *)
Rated voltage U
r
110 or 220 V
Operating range
0 - 340 V
Thermal withstand
450 V for 10 s
420 V continuously
Burden
< 20 mVA at 110 V
< 80 mVA at 220 V
*) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency
SEMOD53376-2 v6
Table 30: CT and VT circuit connectors
Connector type
Rated voltage and current
Maximum conductor area
Screw compression type
250 V AC, 20 A
4 mm
2
(AWG12)
2 x 2.5 mm
2
(2 x AWG14)
Terminal blocks suitable for ring lug terminals
250 V AC, 20 A
4 mm
2
(AWG12)
Section 3
1MRK 502 066-UUS B
Analog inputs
80
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...