21.9.4
Settings
SEMOD55783-1 v2
SEMOD130357-4 v3
Settings
DFTRefExtOut and DFTReference shall be set to default value
InternalDFTRef if no VT inputs are available. Internal nominal frequency DFT
reference is then the reference.
PID-3405-SETTINGS v4
Table 985: SMAI1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
DFTRefExtOut
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference for external output
DFTReference
InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
-
-
InternalDFTRef
DFT reference
ConnectionType
Ph-N
Ph-Ph
-
-
Ph-N
Input connection type
AnalogInputType
Voltage
Current
-
-
Voltage
Analog input signal type
Table 986: SMAI1 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Negation
Disabled
NegateN
Negate3Ph
NeN
-
-
Disabled
Negation
MinValFreqMeas
5 - 200
%
1
10
Limit for frequency calculation in % of
VBase
Section 21
1MRK 502 066-UUS B
Basic IED functions
1266
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...