8.3.8
Technical data
IP11450-1 v1
M12340-2 v8
Table 226: EFPIOC (50N) technical data
Function
Range or value
Accuracy
Trip current
(5-2500)% of lBase
±1.0% of I
n
at I ≤ I
n
±1.0% of I
n
at I > I
n
Reset ratio
> 95% at (50–2500)% of lBase
-
Trip time at 0 to 2 x I
set
Min. = 15 ms
Max. = 25 ms
-
Reset time at 2 to 0 x I
set
Min. = 15 ms
Max. = 25 ms
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Trip time at 0 to 10 x I
set
Min. = 5 ms
Max. = 15 ms
-
Reset time at 10 to 0 x I
set
Min. = 25 ms
Max. = 35 ms
-
Critical impulse time
2 ms typically at 0 to 10 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
8.4
Four step residual overcurrent protection, (Zero
sequence or negative sequence directionality) EF4PTOC
(51N/67N)
IP14509-1 v6
8.4.1
Identification
M14881-1 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step residual overcurrent
protection
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN-US
51N_67N
8.4.2
Functionality
M13667-3 v18
The four step residual overcurrent protection EF4PTOC (51N/67N) has an inverse or definite time
delay independent for each step.
All IEC and ANSI time-delayed characteristics are available together with an optional user defined
characteristic.
EF4PTOC (51N/67N) can be set directional or non-directional independently for each of the steps.
Section 8
1MRK 502 066-UUS B
Current protection
470
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...