7.13.8.4
Simplified logic diagram
GUID-F92413ED-371C-4962-AF72-7BF8D5A188C2 v1
V
Rshunt
ROTIPHIZ (64R)
REX060
REG670
1
I
V
v_i_ref
v_v_ref
X
S
K1
K2
Compare &
Evaluate
ZRef1
ZRef2
3
2
4
5
6
7
ANSI10000327_1_en.vsd
bare
Z
Measured
Z
Inj
I
Inj
V
¸
R
f
inj
ANSI10000327 V1 EN-US
Figure 218: Simplified logic diagram for sensitive rotor earth fault protection, injection based
ROTIPHIZ (64R)
1
The sensitive rotor earth fault protection function receives amplified injected voltage and current via
the REX060 unit as two voltages signals. (Voltage inputs in the IED)
2
The phasor of injected voltage V
Inj
and phasor of injected current I
Inj
is calculated by using special filter
from raw samples. Observe that phasors are calculated for the injected frequency.
3
The complex bare impedance is calculated from V
inj
/ I
inj
.
4, 5
The complex measured impedance is derived as Z
Measured
= Z
bare
*
k1 + k2 [Ω].
6
The fault resistance (R
f
) is calculated from the complex measured impedance and a selected complex
reference.
7
Selection of one (out of maximum 2) Z
Ref
.
Section 7
1MRK 502 066-UUS B
Impedance protection
406
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...