7.2.3
Function block
M13147-3 v4
FDPSPDIS (21)
I3P*
V3P*
BLOCK
DIRCND
TRIP
BFI
FWD_A
FWD_B
FWD_C
FWD_G
REV_A
REV_B
REV_C
REV_G
NDIR_A
NDIR_B
NDIR_C
NDIR_G
FWD_1PH
FWD_2PH
FWD_3PH
PHG_FLT
PHPH_FLT
PHSELZ
DLECND
ANSI14000047-1-en.vsd
ANSI10000047 V2 EN-US
Figure 81: FDPSPDIS (21) function block
7.2.4
Signals
PID-3642-INPUTSIGNALS v5
Table 93: FDPSPDIS (21) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
V3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
DIRCND
INTEGER
0
External directional condition
PID-3642-OUTPUTSIGNALS v5
Table 94: FDPSPDIS (21) Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip by pilot communication scheme logic
BFI
BOOLEAN
Start in any phase or loop
FWD_A
BOOLEAN
Fault detected in phaseA - forward direction
FWD_B
BOOLEAN
Fault detected in phase B - forward direction
FWD_C
BOOLEAN
Fault detected in phase C - forward direction
FWD_G
BOOLEAN
Ground fault detected in forward direction
REV_A
BOOLEAN
Fault detected in phase A- reverse direction
REV_B
BOOLEAN
Fault detected in phase B - reverse direction
REV_C
BOOLEAN
Fault detected in phase C - reverse direction
Table continues on next page
Section 7
1MRK 502 066-UUS B
Impedance protection
198
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...