16.8.3
Function block
SEMOD54336-4 v3
IEC05000346-2-en.vsd
RANGE_XP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346 V2 EN-US
Figure 567: RANGE_XP function block
16.8.4
Signals
SEMOD53803-1 v2
PID-3819-INPUTSIGNALS v4
Table 786: RANGE_XP Input signals
Name
Type
Default
Description
RANGE
INTEGER
0
Measured value range
PID-3819-OUTPUTSIGNALS v4
Table 787: RANGE_XP Output signals
Name
Type
Description
HIGHHIGH
BOOLEAN
Measured value is above high-high limit
HIGH
BOOLEAN
Measured value is between high and high-high limit
NORMAL
BOOLEAN
Measured value is between high and low limit
LOW
BOOLEAN
Measured value is between low and low-low limit
LOWLOW
BOOLEAN
Measured value is below low-low limit
16.8.5
Operation principle
SEMOD52462-4 v5
The input signal must be connected to a range output of a measuring function block (CVMMXN,
CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The function block converts the input
integer value to five binary output signals according to
Table 788: Input integer value converted to binary output signals
Measured supervised
value is:
below low-
low limit
between low
‐
low and low
limit
between low
and high limit
between
high-high
and high limit
above high-high limit
Output:
LOWLOW
High
LOW
High
NORMAL
High
HIGH
High
HIGHHIGH
High
Section 16
1MRK 502 066-UUS B
Monitoring
1092
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...