Function
Range or values
Accuracy
Weight
10.58 lbs
Assembling
6 x 0.20 inch screws (3 at bottom and 3 at top)
Rated rotor injection voltage
250 V
Burden, static excitation system X1:1 to X1:7
<
0.5 VA at 100 V external disturbance
Burden, static excitation system X1:1 or X1:7 to 0 V
<
1.0 VA at 100 V external disturbance
Burden, brushless excitation system X1:1 and X1:7 to
0 V
<
1.5 VA at 100 V external disturbance
Installation category
III
Pollution degree
2
GUID-E7B9192F-ABD5-4395-94F2-ED0B2F0DFEB7 v3
Table 1067:REX062 Technical data
Specifications
Values
Case size
8.58 x 5.91 x 9.57 inches (W x D x H)
Weight
9.92 lbs
Assembling
6 x 0.20 inch screws (3 at bottom and 3 at top)
Rated stator injection voltage
240 V
Rated stator voltage
240 V
Burden, injection X1:2 and X1:4
<
25 VA at 12 V ground fault voltage
<
100 VA at 24 V ground fault voltage
Installation category
III
Pollution degree
2
GUID-52764B12-501B-4B46-9703-E3EB95E06509 v3
Table
1068:
Degree of protection
Description
Values
REX060
Front
Panel mounted, front
Rear, sides, top, bottom and connection terminals
IP40
IP54
IP20
REX061 and REX062
Top
Front, rear, sides and bottom
IP41
IP20
1MRK 502 066-UUS B
Section 23
Injection equipment hardware
1369
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...