Theory of operation
SEMOD154224-46 v6
The mho algorithm is based on the phase comparison of an operating phasor and a polarizing
phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or more,
the function operates and gives a trip output.
Phase-to-phase fault
SEMOD154224-240 v2
GUID-46762EB9-50CA-4045-9D39-80B604C66E0F v1
The plain Mho circle has the characteristic as in figure
. The condition for deriving the angle β is
according to equation
(
)
( )
arg
1
arg
set
p
AB
AB
ol
I
Z
V
V
b
-
×
=
-
ANSIEQUATION15027 V1 EN-US
(Equation 99)
where
AB
V
EQUATION1790-
ANSI V1 EN-US
is the voltage vector difference between phases A and B
AB
I
EQUATION1791-
ANSI V1 EN-US
is the current vector difference between phases A and B
Z
set
1
is the positive sequence impedance setting for phase-to-phase fault in zone direction
V
pol
is the polarizing voltage
Z
R FwPPZx
j X FwPPZx
set
1
1
1
=
+ ⋅
IECEQUATION15010 V1 EN-US
(Equation 100)
where
R1FwPPZ
x
is the positive sequence resistive reach for phase-to-phase fault in zone direction for zone x
(x=1-5 and RV)
X1FwPPZ
x
is the positive sequence reactance reach for phase-to-phase fault in zone direction for zone
x (x=1-5 and RV)
The polarized voltage consists of 100% memorized positive sequence voltage (V
AB
for phase A to B
fault). The memorized voltage will prevent collapse of the mho circle for close in faults.
Operation occurs if 90°≤β≤270°.
1MRK 502 066-UUS B
Section 7
Impedance protection
351
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...