Section 7
Impedance protection
7.1
Distance measuring zones, quadrilateral characteristic
ZMQPDIS (21), ZMQAPDIS (21), ZDRDIR (21D)
IP14498-1 v4
7.1.1
Identification
M14852-1 v6
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance protection zone,
quadrilateral characteristic (zone 1)
ZMQPDIS
S00346 V1 EN-US
21
Distance protection zone,
quadrilateral characteristic (zone
2-5)
ZMQAPDIS
S00346 V1 EN-US
21
Directional impedance quadrilateral
ZDRDIR
Z<->
IEC09000167 V1 EN-US
21D
7.1.2
Functionality
M13787-3 v13
The line distance protection is an up to five (depending on product variant) zone full scheme
protection function with three fault loops for phase-to-phase faults and three fault loops for
phase-to-ground faults for each of the independent zones. Individual settings for each zone in
resistive and reactive reach gives flexibility for use as back-up protection for transformer
connected to overhead lines and cables of different types and lengths.
ZMQPDIS (21) together with Phase selection with load encroachment FDPSPDIS (21) has
functionality for load encroachment, which increases the possibility to detect high resistive faults
on heavily loaded lines, as shown in figure
1MRK 502 066-UUS B
Section 7
Impedance protection
177
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...