22.2.11.5
Monitored data
PID-4110-MONITOREDDATA v4
Table 1033:MIM Monitored data
Name
Type
Values (Range)
Unit
Description
STATUS
BOOLEAN
0=Ok
1=Error
-
Milliampere input module status
CH1
REAL
-
-
Analog input 1
CH2
REAL
-
-
Analog input 2
CH3
REAL
-
-
Analog input 3
CH4
REAL
-
-
Analog input 4
CH5
REAL
-
-
Analog input 5
CH6
REAL
-
-
Analog input 6
CH1
REAL
-
A
Service value analog input 1
CH2
REAL
-
A
Service value analog input 2
CH3
REAL
-
A
Service value analog input 3
CH4
REAL
-
A
Service value analog input 4
CH5
REAL
-
A
Service value analog input 5
CH6
REAL
-
A
Service value analog input 6
22.2.11.6
Technical data
SEMOD55438-1 v1
M6389-1 v4
Table
1034:
MIM - mA input module
Quantity:
Rated value:
Nominal range:
Input resistance
R
in
= 194 Ohm
-
Input range
±5, ±10, ±20mA
0-5, 0-10, 0-20, 4-20mA
-
Power consumption
each mA-board
each mA input
£
2 W
£
0.1 W
-
22.2.12
Serial and LON communication module (SLM)
IP15583-1 v2
22.2.12.1
Introduction
M14933-3 v4
The serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103, DNP3 and LON
communication. The module has two optical communication ports for plastic/plastic, plastic/
glass or glass/glass. One port is used for serial communication (SPA, IEC 60870-5-103 and DNP3
port) and one port is dedicated for LON communication.
1MRK 502 066-UUS B
Section 22
IED hardware
1319
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...