![ABB Relion 670 series Technical Manual Download Page 1338](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_30452261338.webp)
22.2.18.3
Technical data
SEMOD55690-1 v1
SEMOD55693-2 v5
Table
1045:
GPS – Antenna and cable
Function
Value
Max antenna cable attenuation
26 db @ 1.6 GHz
Antenna cable impedance
50 ohm
Lightning protection
Must be provided externally
Antenna cable connector
SMA in receiver end
TNC in antenna end
Accuracy
+/-1μs
22.2.19
IRIG-B time synchronization module IRIG-B
SEMOD141102-1 v1
22.2.19.1
Introduction
SEMOD141113-4 v7
The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from a
station clock.
The Pulse Per Second (PPS) input shall be used for synchronizing when IEC 61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.
22.2.19.2
Design
SEMOD141098-4 v3
The IRIG-B module has two inputs. One input is for the IRIG-B that can handle both a pulse-width
modulated signal (also called unmodulated) and an amplitude modulated signal (also called sine
wave modulated). The other is an optical input type ST for optical pulse-width modulated signal
(IRIG-B 00X).
Section 22
1MRK 502 066-UUS B
IED hardware
1332
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...