Table 175: LEXPDIS (40) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
MeasureMode
PosSeq
AB
BC
CA
-
-
PosSeq
Measuring mode (PosSeq, AB, BC, CA)
Table 176: LEXPDIS (40) Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
InvertCTcurr
No
Yes
-
-
No
Invert CT current
7.12.6
Monitored data
PID-3665-MONITOREDDATA v4
Table 177: LEXPDIS (40) Monitored data
Name
Type
Values (Range)
Unit
Description
XOHM
REAL
-
Ohm
Reactance in Primary Ohms
XPERCENT
REAL
-
%
Reactance in percent of Zbase
ROHM
REAL
-
Ohm
Resistance in Primary Ohms
RPERCENT
REAL
-
%
Resistance in percent of Zbase
7.12.7
Operation principle
SEMOD156166-4 v6
The Loss of excitation (LEXPDIS ,40) protection in the IED measures the apparent impedance seen
out from the generator.The measurement loop of apparent impedance can be chosen as the
positive sequence loop or any one of the three phase-to-phase loops depending on the available
current and voltage signals. It is recommended to use positive sequence quantities for function
operation.
Section 7
1MRK 502 066-UUS B
Impedance protection
390
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...