21.3.2
Function block
SEMOD54888-4 v5
TESTMODE
IED_TEST
TEST
IED_TEST
BLOCK
NOEVENT
INPUT
SETTING
IEC61850
IEC14000072-1-en.vsd
IEC09000219 V2 EN-US
Figure 634: TESTMODE function block
21.3.3
Signals
IP9680-1 v2
PID-3995-INPUTSIGNALS v2
Table 972: TESTMODE Input signals
Name
Type
Default
Description
IED_TEST
BOOLEAN
0
Activate IED test mode
PID-3995-OUTPUTSIGNALS v2
Table 973: TESTMODE Output signals
Name
Type
Description
TEST
BOOLEAN
In test via IED TEST or via LD0 Mode
IED_TEST
BOOLEAN
IED test mode is active
BLOCK
BOOLEAN
Active when LD0 is blocked or test blocked
NOEVENT
BOOLEAN
Event disabled during test mode
INPUT
BOOLEAN
IED TEST input is active
SETTING
BOOLEAN
IED test mode setting is On
IEC61850
BOOLEAN
Active when LD0 Mode is in Blocked, Test or Test blocked
21.3.4
Settings
IP11343-1 v2
PID-6584-SETTINGS v4
Table 974: TESTMODE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IEDTestMode
Disabled
Enabled
-
-
Disabled
Activate IED Test mode
EventDisable
Disabled
Enabled
-
-
Disabled
Event disable during test mode
BlockAllFunc
Disabled
Enabled
-
-
Enabled
Block all functions when entering IED test
mode
CmdTestEd1
Disabled
Enabled
-
-
Disabled
Require test bit in command at test mode
(only for IEC61850 Ed1)
Section 21
1MRK 502 066-UUS B
Basic IED functions
1256
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...