Name
Type
Default
Description
INPUT9
BOOLEAN
0
Binary input 9
INPUT10
BOOLEAN
0
Binary input 10
INPUT11
BOOLEAN
0
Binary input 11
INPUT12
BOOLEAN
0
Binary input 12
INPUT13
BOOLEAN
0
Binary input 13
INPUT14
BOOLEAN
0
Binary input 14
INPUT15
BOOLEAN
0
Binary input 15
INPUT16
BOOLEAN
0
Binary input 16
PID-4126-OUTPUTSIGNALS v3
Table 596: ALMCALH Output signals
Name
Type
Description
ALARM
BOOLEAN
OR function betweeen inputs 1 to 16
15.3.5
Settings
PID-4126-SETTINGS v3
Table 597: ALMCALH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
15.3.6
Operation principle
GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2
The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM output
signal. The function block incorporates internal logic OR gate in order to provide grouping of
connected input signals to the output ALARM signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output signal
will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal.
ALARM
Input 1
Input 16
1
ANSI13000191-1-en.vsd
200 ms
0
ANSI13000191 V1 EN-US
Figure 490: Group alarm logic
Section 15
1MRK 502 066-UUS B
Logic
950
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...