PID-3807-INPUTSIGNALS v4
Table 660: ORQT Input signals
Name
Type
Default
Description
INPUT1
BOOLEAN
0
Input signal 1
INPUT2
BOOLEAN
0
Input signal 2
INPUT3
BOOLEAN
0
Input signal 3
INPUT4
BOOLEAN
0
Input signal 4
INPUT5
BOOLEAN
0
Input signal 5
INPUT6
BOOLEAN
0
Input signal 6
PID-3807-OUTPUTSIGNALS v4
Table 661: ORQT Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
15.7.6.3
Technical data
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1
Table 662: Number of ORQT instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
ORQT
-
20
100
15.7.7
Pulse timer function block PULSETIMERQT
GUID-5CB71BD1-58A0-4A06-9207-6DAE389B5288 v2
GUID-D930E5A7-C564-4464-B97F-C72B4801C917 v3
The pulse timer function block (PULSETIMERQT) can be used, for example, for pulse extensions or
for limiting the operation time of the outputs. PULSETIMERQT has a settable output pulse length.
When the input goes to 1, the output will be 1 for the time set by the time delay parameter
t. Then
it returns to 0.
When the output changes value, the time stamp of the output signal is updated.
The supported “quality” state bits are propagated from the input to the output at each execution
cycle. A change of these bits will not lead to an updated time stamp on the output.
PULSETIMERQT can propagate the quality, value and the time stamps of the signals via IEC61850.
1MRK 502 066-UUS B
Section 15
Logic
975
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...