![ABB Relion 670 series Technical Manual Download Page 717](http://html.mh-extra.com/html/abb/relion-670-series/relion-670-series_technical-manual_3045226717.webp)
a
b
b>a
Selected current
PickupCurr_UC1
Operation_UC1=On
Bin input: BLKUC1
PU_UC1
en05000750_ansi.vsd
TRUC1
Bin input: BLKUC1TR
0-DEF
AND
AND
0
ANSI05000750 V1 EN-US
Figure 380: Simplified internal logic diagram for built-in first undercurrent step that is, UC1 (step UC2 has
the same internal logic)
a
b
a>b
Selected voltage
PickupVolt_OV1
Operation_OV1=On
BLKOV1
Inverse time
selected
en05000751_ansi.vsd
Inverse
0-DEF
DEF time
selected
PU_OV1
TROV1
AND
BLKTROV1
AND
OR
0
ANSI05000751 V1 EN-US
Figure 381: Simplified internal logic diagram for built-in first overvoltage step OV1 (step OV2 has the same
internal logic)
1MRK 502 066-UUS B
Section 11
Multipurpose protection
711
Technical manual