Name
Type
Description
OUTPUT15
BOOLEAN
Output 15
OUTPUT16
BOOLEAN
Output 16
VALID
BOOLEAN
Output data is valid
PID-399-OUTPUTSIGNALS v9
Table 925: MULTICMDSND Output signals
Name
Type
Description
ERROR
BOOLEAN
MultiSend error
18.17.5
Settings
SEMOD119927-1 v2
PID-400-SETTINGS v9
Table 926: MULTICMDRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tMaxCycleTime
0.050 - 200.000
s
0.001
11.000
Maximum cycle time between receptions
of input data
tMinCycleTime
0.000 - 200.000
s
0.001
0.000
Minimum cycle time between receptions of
input data
Mode
Steady
Pulsed
-
-
Steady
Mode for output signals
tPulseTime
0.000 - 60.000
s
0.001
0.200
Pulse length for multi command outputs
PID-399-SETTINGS v9
Table 927: MULTICMDSND Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tMaxCycleTime
0.000 - 200.000
s
0.001
5.000
Maximum time interval between
transmission of output data
tMinCycleTime
0.000 - 200.000
s
0.001
0.000
Minimum time interval between
transmission of output data
18.17.6
Operation principle
M14793-3 v3
There are 10 instances of the MULTICMDSND function block. The first two are fast (8 ms cycle
time) while the others are slow (100 ms cycle time). Each instance has 16 binary inputs, to which 16
independent signals can be connected. Connected signals are sent through MULTICMDSND to the
receiving equivalent, MULTICMDRCV, located on a different IED.
The MULTICMDRCV function block has 16 binary outputs, all controlled through the command
block of one or many MULTICMDSND function blocks. There are 60 instances of the
MULTICMDRCV where the first 12 are fast (8 ms), and the others are slow (100 ms). Additionally,
the MULTICMDRCV has a supervision function, which sets the output connector "VALID" to 0 (zero)
if its block does not receive any data within the time defined by tMaxCycleTime.
LON connections are established using LON network tool (LNT).
Section 18
1MRK 502 066-UUS B
Station communication
1208
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...