IEC 61850
ANSI
Function description
REG670
(Customized)
OEXPVPH
24
Overexcitation protection
0-2
VDCPTOV
60
Voltage differential protection
0-2
STEFPHIZ
59THD
100% stator earth fault protection, 3rd harmonic
based
0-1
LOVPTUV
27
Loss of voltage check
Frequency protection
SAPTUF
81
Underfrequency protection
0-6
SAPTOF
81
Overfrequency protection
0-6
SAPFRC
81
Rate-of-change frequency protection
0-3
FTAQFVR
81A
Frequency time accumulation protection
0-12
Multipurpose protection
CVGAPC
General current and voltage protection
1-12
General calculation
SMAIHPAC
Multipurpose filter
0-6
1) 67 requires voltage
2) 67N requires voltage
2.3
Control and monitoring functions
GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v12
IEC 61850
ANSI
Function description
Generator
REG670
Control
SESRSYN
25
Synchrocheck, energizing check and
synchronizing
0-2
APC15
3
Apparatus control for single bay, max 15
apparatuses (2CBs) incl. interlocking
APC30
3
Apparatus control for up to 6 bays, max 30
apparatuses (6CBs) incl. interlocking
0-1
QCBAY
Apparatus control
1+5/APC30
LOCREM
Handling of LRswitch positions
1+5/APC30
LOCREMCTRL
LHMI control of PSTO
1+5/APC30
TR1ATCC
90
Automatic voltage control for tap changer,
single control
TR8ATCC
90
Automatic voltage control for tap changer,
parallel control
TCMYLTC
84
Tap changer control and supervision, 6 binary
inputs
0-4
TCLYLTC
84
Tap changer control and supervision, 32
binary inputs
0-4
Table continues on next page
1MRK 502 066-UUS B
Section 2
Available functions
59
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...