Name
Type
Default
Description
6189_EX1
BOOLEAN
0
External condition for apparatus 6189
6189_EX2
BOOLEAN
0
External condition for apparatus 6189
6289_EX1
BOOLEAN
0
External condition for apparatus 6289
6289_EX2
BOOLEAN
0
External condition for apparatus 6289
PID-3501-OUTPUTSIGNALS v5
Table 463: BH_CONN (3) Output signals
Name
Type
Description
152CLREL
BOOLEAN
Closing of 152 is allowed
152CLITL
BOOLEAN
Closing of 152 is not allowed
6189REL
BOOLEAN
Switching of 6189 is allowed
6189ITL
BOOLEAN
Switching of 6189 is not allowed
6289REL
BOOLEAN
Switching of 6289 is allowed
6289ITL
BOOLEAN
Switching of 6289 is not allowed
189GREL
BOOLEAN
Switching of 189G is allowed
189GITL
BOOLEAN
Switching of 189G is not allowed
289GREL
BOOLEAN
Switching of 289G is allowed
289GITL
BOOLEAN
Switching of 289G is not allowed
14.2.9
Interlocking for double CB bay DB (3)
IP14167-1 v2
14.2.9.1
Identification
GUID-D6D10255-2818-44E4-A44E-DF623161C486 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for double CB bay
DB_BUS_A
-
3
Interlocking for double CB bay
DB_BUS_B
-
3
Interlocking for double CB bay
DB_LINE
-
3
14.2.9.2
Functionality
M13585-3 v10
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A (3), DB_BUS_B
(3) and DB_LINE (3) functions are used for a line connected to a double busbar arrangement
according to figure
Section 14
1MRK 502 066-UUS B
Control
798
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...