The calculated
R
m
and
X
m
values are updated each sample and compared with the set zone reach.
The adaptive tripping counter counts the number of permissive tripping results. This effectively
removes any influence of errors introduced by the capacitive voltage transformers or by other
factors.
The directional evaluations are performed simultaneously in both forward and reverse directions,
and in all six fault loops. Positive sequence voltage and a phase locked positive sequence memory
voltage are used as a reference. This ensures unlimited directional sensitivity for faults close to
the IED point.
7.1.7.5
Directional impedance element for quadrilateral characteristics
M16923-139 v6
The evaluation of the directionality takes place in Directional impedance quadrilateral function
are used to classify that the fault is in forward
direction for phase-to-ground fault and phase-to-phase fault.
1
1
1
0.8
1
0.2
1
arg
Re
L
L M
L
V
V
ArgDir
ArgNeg
s
I
×
+
×
-
<
<
EQUATION1552 V2 EN-US
(Equation 43)
For the AB element, the equation in forward direction is according to.
1 2
1 2
1 2
0.8
1
0.2
1
arg
Re
L L
L L M
L L
V
V
ArgDir
ArgNeg
s
I
×
+
×
-
<
<
EQUATION1553 V2 EN-US
(Equation 44)
where:
AngDir
is the setting for the lower boundary of the forward directional characteristic, by default set to 15 (=
-15 degrees) and
AngNegRes is the setting for the upper boundary of the forward directional characteristic, by default set to 115
degrees, see figure
.
V1
A
is positive sequence phase voltage in phase A
V1
AM
is positive sequence memorized phase voltage in phase A
I
A
is phase current in phase A
V1
AB
is voltage difference between phase A and B (B lagging A)
V1
ABM
is memorized voltage difference between phase A and B (B lagging A)
I
AB
is current difference between phase A and B (B lagging A)
The setting of
AngDir and AngNegRes is by default set to 15 (= -15) and 115 degrees respectively
(as shown in figure
). It should not be changed unless system studies have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the output STDIRCND.
STDIR=
FWD_A*1+FWD_B*2+FWD_C*4+FWD_AB*8+
+FWD_BC*16+FWD_CA*32+REV_A*64+REV_B*128+REV_C*256+
+REV_AB*512+REV_BC*1024+REV_CA*2048
1MRK 502 066-UUS B
Section 7
Impedance protection
191
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...