Name
Values (Range)
Unit
Step
Default
Description
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
-
-
Disabled
Unsolicited response, event class mask
UROfflineRetry
0 - 10
-
1
5
Unsolicited response retries before off-line
retry mode
tVRRetryDelay
0.00 - 60.00
s
0.01
5.00
Unsolicited response retry delay in s
tVROfflRtryDel
0.00 - 60.00
s
0.01
30.00
Unsolicited response off-line retry delay in
s
UREvCntThold1
1 - 100
-
1
5
Unsolicited response class 1 event count
report treshold
tVREvBufTout1
0.00 - 60.00
s
0.01
5.00
Unsolicited response class 1 event buffer
timeout
UREvCntThold2
1 - 100
-
1
5
Unsolicited response class 2 event count
report treshold
tVREvBufTout2
0.00 - 60.00
s
0.01
5.00
Unsolicited response class 2 event buffer
timeout
UREvCntThold3
1 - 100
-
1
5
Unsolicited response class 3 event count
report treshold
tVREvBufTout3
0.00 - 60.00
s
0.01
5.00
Unsolicited response class 3 event buffer
timeout
DelOldBufFull
No
Yes
-
-
No
Delete oldest event when buffer is full
ExtTimeFormat
LocalTime
UTC
-
-
UTC
External time format
DNPToSetTime
No
Yes
-
-
No
Allow DNP to set time in IED
tSynchTimeout
30 - 3600
s
1
1800
Time synch timeout before error status is
generated
TSyncReqAfTout
No
Yes
-
-
No
Time synchronization request after
timeout
Averag3TimeReq
No
Yes
-
-
No
Use average of 3 time requests
PairedPoint
No
Yes
-
-
Yes
Enable paired point
tSelectTimeout
1.0 - 60.0
s
0.1
30.0
Select timeout
tBrokenConTout
0 - 3600
s
1
0
Broken connection timeout
tKeepAliveT
0 - 3600
s
1
10
Keep-Alive timer
14.9.6
Operation principle
SEMOD158597-4 v5
AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
1MRK 502 066-UUS B
Section 14
Control
933
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...