Function
Range or value
Accuracy
Reset time at 10 to 0 x I
set
Min. = 20 ms
Max. = 35 ms
-
Undercurrent:
Pickup time at 2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
-
Reset time at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
-
Overcurrent:
Inverse time characteristics, see table
16 curve types
See table
,
and table
Overcurrent:
Minimum operate time for inverse
curves, step 1 - 2
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Voltage level where voltage memory
takes over
(0.0 - 5.0)% of VBase
±0.5% of V
n
Pickup overvoltage, step 1 - 2
(2.0 - 200.0)% of VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Pickup undervoltage, step 1 - 2
(2.0 - 150.0)% of VBase
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Independent time delay, overvoltage at
0.8 to 1.2 x V
set
, step 1 - 2
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Independent time delay, undervoltage
at 1.2 to 0.8 x V
set
, step 1 - 2
(0.00 - 6000.00) s
±0.2% or ±35 ms whichever is
greater
Overvoltage:
Pickup time at 0.8 to 1.2 x V
set
Min. = 15 ms
Max. = 30 ms
-
Reset time at 1.2 to 0.8 x V
set
Min. = 15 ms
Max. = 30 ms
-
Undervoltage:
Pickup time at 1.2 to 0.8 x V
set
Min. = 15 ms
Max. = 30 ms
-
Reset time at 1.2 to 0.8 x V
set
Min. = 15 ms
Max. = 30 ms
-
Overvoltage:
Inverse time characteristics, see table
4 curve types
See table
Undervoltage:
Inverse time characteristics, see table
3 curve types
See table
High and low voltage limit, voltage
dependent operation, step 1 - 2
(1.0 - 200.0)% of VBase
±1.0% of V
n
at V ≤ V
n
±1.0% of V at V > V
n
Directional function
Settable: NonDir, forward and reverse
-
Relay characteristic angle
(-180 to +180) degrees
±2.0 degrees
Relay trip angle
(1 to 90) degrees
±2.0 degrees
Reset ratio, overcurrent
> 95%
-
Table continues on next page
1MRK 502 066-UUS B
Section 11
Multipurpose protection
713
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...