Name
Type
Description
CMDBIT30
BOOLEAN
Command out bit 30
CMDBIT31
BOOLEAN
Command out bit 31
CMDBIT32
BOOLEAN
Command out bit 32
14.9.5
Settings
PID-3776-SETTINGS v4
Table 560: AUTOBITS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PID-3715-SETTINGS v6
Table 561: DNPGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
PID-4105-SETTINGS v5
Table 562: CHSERRS485 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BaudRate
300 Bd
600 Bd
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd
57600 Bd
115200 Bd
-
-
9600 Bd
Baud-rate for serial port
Table 563: CHSERRS485 Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
DLinkConfirm
Never
Sometimes
Always
-
-
Never
Data-link confirm
tDLinkTimeout
0.000 - 60.000
s
0.001
2.000
Data-link confirm timeout in s
DLinkRetries
0 - 255
-
1
3
Data-link maximum retries
tRxToTxMinDel
0.000 - 60.000
s
0.001
0.000
Rx to Tx minimum delay in s
ApLayMaxRxSize
20 - 2048
-
1
2048
Application layer maximum Rx fragment
size
ApLayMaxTxSize
20 - 2048
-
1
2048
Application layer maximum Tx fragment
size
Table continues on next page
1MRK 502 066-UUS B
Section 14
Control
919
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...