14.1.8
Technical data
M12359-1 v12
Table 447: SESRSYN (25) technical data
Function
Range or value
Accuracy
Phase shift,
j
line
-
j
bus
(-180 to 180) degrees
-
Voltage high limit for synchronism check
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Reset ratio, synchronism check
> 95%
-
Frequency difference limit between bus and
line for synchronism check
(0.003-1.000) Hz
±2.5 mHz
Phase angle difference limit between bus and
line for synchronism check
(5.0-90.0) degrees
±2.0 degrees
Voltage difference limit between bus and line
for synchronism check
(0.02-0.5) p.u
±0.5% of V
n
Time delay output for synchronism check
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Frequency difference minimum limit for
synchronizing
(0.003-0.250) Hz
±2.5 mHz
Frequency difference maximum limit for
synchronizing
(0.050-0.500) Hz
±2.5 mHz
Maximum allowed frequency rate of change
(0.000-0.500) Hz/s
±10.0 mHz/s
Breaker closing pulse duration
(0.050-60.000) s
±0.2% or ±15 ms whichever is
greater
tMaxSynch, which resets synchronizing
function if no close has been made before set
time
(0.000-6000.00) s
±0.2% or ±35 ms whichever is
greater
Minimum time to accept synchronizing
conditions
(0.000-60.000) s
±0.2% or ±35 ms whichever is
greater
Voltage high limit for energizing check
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Reset ratio, voltage high limit
> 95%
-
Voltage low limit for energizing check
±0.5% of V
n
Reset ratio, voltage low limit
< 105%
-
Maximum voltage for energizing
±0.5% of V
n
at V ≤ V
n
±0.5% of V at V > V
n
Time delay for energizing check when voltage
jumps from 0 to 90% of Vrated
(0.000-60.000) s
±0.2% or ±100 ms whichever is
greater
Trip time for synchrocheck function when
angle difference between bus and line jumps
from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2
degrees
Min. = 15 ms
Max. = 30 ms
–
Trip time for energizing function when voltage
jumps from 0 to 90% of Vrated
Min. = 70 ms
Max. = 90 ms
–
Section 14
1MRK 502 066-UUS B
Control
764
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...