TCMYLTC (84) and TCLYLTC (84) also serve the purpose of giving information about tap position
to the transformer differential protection T2WPDIF (87T) and T3WPDIF (87T).
14.4.11
Technical data
SEMOD175215-2 v12
Table 544: TCMYLTC (84) and TLCYLTC (84) technical data
Function
Range or value
Accuracy
Transformer reactance
(0.1–200.0)Ω, primary
-
Time delay for lower command when fast step
down mode is activated
(1.0–100.0) s
-
Voltage control set voltage
(85.0–120.0)% of VBase
±0.25 % of V
n
Outer voltage deadband
(0.2–9.0)% of VBase
-
Inner voltage deadband
(0.1–9.0)% of VBase
-
Upper limit of busbar voltage
(80–180)% of VBase
±0.5% of V
n
Lower limit of busbar voltage
(70–120)% of VBase
±0.5% of V
n
Undervoltage block level
(50–120)% of VBase
±0.5% of V
n
Time delay (long) for automatic control
commands
(3–1000) s
±0.2% or ±600 ms
whichever is greater
Time delay (short) for automatic control
commands
(1–1000) s
±0.2% or ±600 ms
whichever is greater
Minimum operating time in inverse mode
(3–120) s
±0.2% or ±600 ms
whichever is greater
Line resistance
(0.00–150.00)Ω, primary
-
Line reactance
(-150.00–150.00)Ω, primary
-
Load voltage adjustment constants
(-20.0–20.0)% of VBase
-
Load voltage auto correction
(-20.0–20.0)% of VBase
-
Duration time for the reverse action block
signal
(30–6000) s
±0.2% or ±600 ms
whichever is greater
Current limit for reverse action block
(0–100)% of I1Base
-
Overcurrent block level
(5–250)% of I1Base
±1.0% of I
n
at I≤I
n
±1.0% of I at I>I
n
Level for number of counted raise/lower
within one hour
(0–30) operations/hour
-
Level for number of counted raise/lower
within 24 hours
(0–100) operations/day
-
Time window for hunting alarm
(1–120) minutes
-
Hunting detection alarm, max operations/
window
(3–30) operations/window
-
Alarm level of active power in forward and
reverse direction at (10-200)% of S
n
and
(85-120)% of VBase
(-9999.99–9999.99) MW
±1.0% of S
n
Alarm level of reactive power in forward and
reverse direction at (10-200)% of S
n
and
(85-120)% of VBase
(-9999.99–9999.99) MVAr
±1.0% of S
n
Table continues on next page
1MRK 502 066-UUS B
Section 14
Control
905
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...