Section 3: Functions and features
Model 2281S-20-6 DC Power Supply and Battery Simulator Reference Manual
3-68
077114601 / March 2019
Using SCPI commands:
Connect the battery to the instrument.
Send the command:
:BATT:TEST:VOLT V1
Set the discharging target voltage to V1.
Send the commands:
:BATT:TEST:SENS:AH:VFUL V2
:BATT:TEST:SENS:AH:ILIM A2
:BATT:TEST:SENS:AH:ESRI S30
Set the V-Full to V2.
Set the maximum charging limit to A2.
Set the sampling interval to 30 s.
Send the commands:
:BATT:TEST:SENS:AH:EXEC STAR
:STAT:OPER:INST:ISUM:COND?
:BATT:TEST:SENS:AH:GMOD:RANG 2.5, 3.7
:BATT:TEST:SENS:AH:GMOD:SAVE:INTE 1
Start the measurement.
Query whether the measurement is done.
Set the range for generating battery model if needed.
Save the battery model to internal memory.
The values V1, V2, A1, and A2 are to be provided by the battery manufacturer, and improper