Part 7: Common Reference Material
7 - 17
(2) Parameter setting (for MR-J4-_B_series)
POINT
With MR-J4-_B_, the deceleration to a stop function is enabled in the factory
setting. To disable the deceleration to a stop function, set [Pr. PA04] to "0 _ _ _".
Number
Abbrevi-
ation
Name and function
Initial
value
[unit]
Setting
range
PA04 *AO
P1
Function selection A-1
This is used to select the forced stop input and forced stop deceleration function.
Refer to Name and
function column.
Setting digit
Explanation
Initial
value
_ _ _ x
For manufacturer setting
0h
_ _ x _
0h
_ x _ _
Servo forced stop selection
0: Enabled (The forced stop input EM2 or EM1 is used.)
1: Disabled
(The forced stop input EM2 and EM1 are not used.)
Refer to the following table for details.
0h
x _ _ _
Forced stop deceleration function selection
0: Forced stop deceleration function disabled (EM1)
2: Forced stop deceleration function enabled (EM2)
Refer to the following table for details.
2h
Setting
value
EM2/EM1
selection
Deceleration method
EM2 or EM1 is off
Alarm occurred
0 0 _ _
EM1
MBR (Electromagnetic brake
interlock) turns off without
the forced stop deceleration.
MBR (Electromagnetic brake
interlock) turns off without the
forced stop deceleration.
2 0 _ _
EM2
MBR (Electromagnetic brake
interlock) turns off after the
forced stop deceleration.
MBR (Electromagnetic brake
interlock) turns off after the
forced stop deceleration.
0 1 _ _
Not using
EM2 or
EM1
MBR (Electromagnetic brake
interlock) turns off without the
forced stop deceleration.
2 1 _ _
Not using
EM2 or
EM1
MBR (Electromagnetic brake
interlock) turns off after the
forced stop deceleration.
1.2.5 24 V DC power supply for interface: built-in
⇒
outside supply requisite
These are the recommended specifications for a 24 V DC power source for interface that is required for
renewal.
Select according to the following specifications.
Item
MR-J2S series
MR-J2M series
→
MR-J4 series
For interface
24 V DC power supply
Servo amplifier
Internal power supply
External supply required
24 V DC ±10%
Power capacity
MR-J4-_A_: 500 mA or more
MR-J4-_B_: 300 mA or more
External supply
24 V DC ±10%
Power capacity: 80 mA or more
External supply
24 V DC ±10%
Power capacity: 300 mA or more
Содержание MELSERVO-J2-Super Series
Страница 18: ...Part 1 Summary of MR J2S MR J2M Replacement 1 1 Part 1 Summary of MR J2S MR J2M Replacement ...
Страница 31: ...Part 1 Summary of MR J2S MR J2M Replacement 1 14 MEMO ...
Страница 109: ...Part 3 Review on Replacement of MR J2S _B_ with MR J4 _B_ 3 32 MEMO ...
Страница 161: ...Part 4 Review on Replacement of MR J2S _CP_ CL_ with MR J4 _A_ RJ 4 52 MEMO ...
Страница 219: ...Part 5 Review on Replacement of MR J2S 30 kW or Higher Capacity Models with MR J4 DU_ 5 58 MEMO ...
Страница 220: ...Part 6 Review on Replacement of MR J2M with MR J4 6 1 Part 6 Review on Replacement of MR J2M with MR J4 ...
Страница 239: ...Part 6 Review on Replacement of MR J2M with MR J4 6 20 MEMO ...
Страница 240: ...Part 7 Common Reference Material 7 1 Part 7 Common Reference Material ...
Страница 284: ...Part 7 Common Reference Material 7 45 Click Update Project ...
Страница 342: ...Part 8 Review on Replacement of Motor 8 1 Part 8 Review on Replacement of Motor ...
Страница 409: ...Part 8 Review on Replacement of Motor 8 68 MEMO ...
Страница 461: ...Part 9 Review on Replacement of Optional Peripheral Equipment 9 52 MEMO ...
Страница 462: ...Part 10 Startup Procedure Manual 10 1 Part 10 Startup Procedure Manual ...
Страница 464: ... Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 Appendix 1 1 Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 ...