Part 5: Review on Replacement of MR-J2S-30 kW or Higher Capacity Models with MR-J4-DU_
5 - 37
5.3 Selection of No-Fuse Breakers, Fuses, and Magnetic Contactors (example)
5.3.1 MR-J2S-series, no-fuse breakers and magnetic contactors (recommended)
Always use one molded-case circuit breaker/one magnetic contactor with one servo amplifier.
Servo amplifier
Converter unit
Molded-case circuit breaker
Magnetic
contactor
Current
Voltage
AC
Power factor improving
DC reactor not used
Power factor improving
DC reactor used
MR-J2S-30KA/B
MR-HP30KA
400 A frame 250 A
225 A frame 225 A
240 V
S-N150
MR-J2S-37KA/B
400 A frame 300 A
400 A frame 300 A
S-N180
MR-J2S-30KA4/B4
MR-HP55KA4
225 A frame 150 A
225 A frame 125 A
600Y/
347 V
S-N95
MR-J2S-37KA4/B4
225 A frame 175 A
225 A frame 150 A
S-N125
MR-J2S-45KA4/B4
225 A frame 225 A
225 A frame 175 A
S-N150
MR-J2S-55KA4/B4
400 A frame 250 A
225 A frame 225 A
S-N180
5.3.2 MR-J4-series, no-fuse breakers, fuses, and magnetic contactors (recommended)
(1) For main circuit power supply
Always use one molded-case circuit breaker and one magnetic contactor with one converter unit. When
using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in
this section.
Converter
unit
Drive unit
Molded-case circuit breaker (Note 1)
Fuse
Magnetic
contactor
(Note 2)
Frame, rated current
Voltage
AC [V]
Class
Current
[A]
Voltage
AC [V]
Power factor
improving DC
reactor not used
Power factor
improving DC
reactor used
MR-CR55K
MR-J4-DU30K_ 225 A frame 175 A
225 A frame 150 A
240
T
300
300
S-N150
MR-J4-DU37K_ 225 A frame 225 A
225 A frame 175 A
400
S-N180
MR-CR55K4
MR-J4-DU30K_4 100 A frame 100 A
100 A frame 80 A
480
175
600
S-N65
MR-J4-DU37K_4 125 A frame 125 A
100 A frame 100 A
200
S-N80
MR-J4-DU45K_4 225 A frame 150 A
125 A frame 125 A
300
S-N95
MR-J4-DU55K_4 225 A frame 175 A
225 A frame 150 A
300
S-N150
Note 1. To comply with the IEC/EN/UL/CSA standard, refer to App. 2.
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less.
Содержание MELSERVO-J2-Super Series
Страница 18: ...Part 1 Summary of MR J2S MR J2M Replacement 1 1 Part 1 Summary of MR J2S MR J2M Replacement ...
Страница 31: ...Part 1 Summary of MR J2S MR J2M Replacement 1 14 MEMO ...
Страница 109: ...Part 3 Review on Replacement of MR J2S _B_ with MR J4 _B_ 3 32 MEMO ...
Страница 161: ...Part 4 Review on Replacement of MR J2S _CP_ CL_ with MR J4 _A_ RJ 4 52 MEMO ...
Страница 219: ...Part 5 Review on Replacement of MR J2S 30 kW or Higher Capacity Models with MR J4 DU_ 5 58 MEMO ...
Страница 220: ...Part 6 Review on Replacement of MR J2M with MR J4 6 1 Part 6 Review on Replacement of MR J2M with MR J4 ...
Страница 239: ...Part 6 Review on Replacement of MR J2M with MR J4 6 20 MEMO ...
Страница 240: ...Part 7 Common Reference Material 7 1 Part 7 Common Reference Material ...
Страница 284: ...Part 7 Common Reference Material 7 45 Click Update Project ...
Страница 342: ...Part 8 Review on Replacement of Motor 8 1 Part 8 Review on Replacement of Motor ...
Страница 409: ...Part 8 Review on Replacement of Motor 8 68 MEMO ...
Страница 461: ...Part 9 Review on Replacement of Optional Peripheral Equipment 9 52 MEMO ...
Страница 462: ...Part 10 Startup Procedure Manual 10 1 Part 10 Startup Procedure Manual ...
Страница 464: ... Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 Appendix 1 1 Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 ...