[Appendix 1] Summary of MR-J4_B_-RJ020 + MR-J4-T20
Appendix 1-61
13.5.3 Parameter setting
[Setting for 22 kW or less]
Set [Pr. 2] adjusting to the regenerative option to be used.
[Setting for 30 kW or more]
POINT
Regenerative options cannot be connected to the drive unit. [Pr. PA02] in the drive
unit must be set to "_ _ 0 0" (do not use regenerative options) or "_ _01". Setting
other than the above will cause [AL. 37 Parameter error].
Set [Pr. PA01] for the converter unit, adjusting to the regenerative option to be used.
0 0
[Pr. 2]
00: The regenerative option is not used
・
For servo amplifier of 100W, regenerative resistor is not used.
・
For servo amplifier of 0.2 kW to 7 kW, built-in regenerative resistor is used.
・
The supplied regenerative resistor or regenerative option is used in the servo amplifier at
11 kW to 22 kW.
01: FR-RC/FR-RC-H/FR-CV/FR-CV-H/FR-BU2/FR-BU2-H
05: MR-RB32
08: MR-RB30
09: MR-RB50 (Cooling fan is needed)
0B: MR-RB31
0C: MR-RB51 (Cooling fan is needed)
0E: When increasing the capabilities by using a cooling fan to cool the supplied regeneration
resistor with the servo amplifier of 11 kW to 22 kW.
10: MR-RB032
11: MR-RB12
13: MR-RB5E
14: MR-RB5E (Cooling fan is needed)
17: MR-RB9F
18: MR-RB9F (Cooling fan is needed)
20: MR-RB3N
21: MR-RB5N (Cooling fan is needed)
23: MR-RB5R
24: 24: MR-RB5R (Cooling fan is needed)
25: MR-RB9P
26: MR-RB9P (Cooling fan is needed)
27: MR-RB9T
28: MR-RB9T (Cooling fan is needed)
80: MR-RB3H-4 (Cooling fan is needed)
81: MR-RB5H-4 (Cooling fan is needed)
82: MR-RB3G-4 (Cooling fan is needed)
83: MR-RB5G-4 (Cooling fan is needed)
84: MR-RB34-4 (Cooling fan is needed)
85: MR-RB54-4 (Cooling fan is needed)
86: MR-RB1L-4
87: MR-RB3M-4 (Cooling fan is needed)
90: MR-RB1H-4
94: MR-RB5K-4
95: MR-RB5K-4 (Cooling fan is needed)
96: MR-RB6B-4
97: MR-RB6B-4 (Cooling fan is needed)
98: MR-RB6K-4
99: MR-RB6K-4 (Cooling fan is needed)
9A: MR-RB60-4
9B: MR-RB60-4 (Cooling fan is needed)
9C: MR-RB3U-4 (Cooling fan is needed)
9D: MR-RB5U-4 (Cooling fan is needed)
Regenerative option selection
00: Not used
12: MR-RB138-4 (3 units)
01: MR-RB139
13: MR-RB137-4
02: MR-RB137 (3 units)
14: MR-RB13V-4 (3 units)
11: MR-RB136-4
[Pr. PA01]
0
0
Содержание MELSERVO-J2-Super Series
Страница 18: ...Part 1 Summary of MR J2S MR J2M Replacement 1 1 Part 1 Summary of MR J2S MR J2M Replacement ...
Страница 31: ...Part 1 Summary of MR J2S MR J2M Replacement 1 14 MEMO ...
Страница 109: ...Part 3 Review on Replacement of MR J2S _B_ with MR J4 _B_ 3 32 MEMO ...
Страница 161: ...Part 4 Review on Replacement of MR J2S _CP_ CL_ with MR J4 _A_ RJ 4 52 MEMO ...
Страница 219: ...Part 5 Review on Replacement of MR J2S 30 kW or Higher Capacity Models with MR J4 DU_ 5 58 MEMO ...
Страница 220: ...Part 6 Review on Replacement of MR J2M with MR J4 6 1 Part 6 Review on Replacement of MR J2M with MR J4 ...
Страница 239: ...Part 6 Review on Replacement of MR J2M with MR J4 6 20 MEMO ...
Страница 240: ...Part 7 Common Reference Material 7 1 Part 7 Common Reference Material ...
Страница 284: ...Part 7 Common Reference Material 7 45 Click Update Project ...
Страница 342: ...Part 8 Review on Replacement of Motor 8 1 Part 8 Review on Replacement of Motor ...
Страница 409: ...Part 8 Review on Replacement of Motor 8 68 MEMO ...
Страница 461: ...Part 9 Review on Replacement of Optional Peripheral Equipment 9 52 MEMO ...
Страница 462: ...Part 10 Startup Procedure Manual 10 1 Part 10 Startup Procedure Manual ...
Страница 464: ... Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 Appendix 1 1 Appendix 1 Summary of MR J4_B_ RJ020 MR J4 T20 ...