Chapter 3 Installation
C
h
a
p
te
r
3
Sort
Terminal
Name
Function Description
Digital
output
FM
(optional
Y2)
High-speed
pulse output
Analog voltage/current input,Choose voltage or
current input by Setting JP3 jumper.
Factory default: voltage input(Grounding: GND)
Communica
tion
Interface
485+
,
485-
Modbus
communication
interface
Modbus communication interface, you can
choose whether to need communication
matching resistance through the DIP switch
(refer to the bit number of the terminal wiring
diagram).
If Profibus communication function is required,
please select KD600 series expansion card and
Profibus DP card.
Relay
output 1
TA-TB
Normally
closed terminal Contact drive capability:
AC250V, 3A, COS
φ=0.4. DC30V, 1A
TA-TC
Normally open
terminal
Relay
output 2
RA-RB
Normally
closed terminal Contact drive capability:
AC250V, 3A, COS
φ=0.4. DC30V, 1A
RA-RC
Normally open
terminal
Keyboard
extension
cable
interface
Control
board
RJ45
interface
External
keyboard
interface
External keyboard interface, can use standard
network cable for external extension.
3.6.3 Signal input terminal wiring instructions:
A. AI analog input terminal:
Because weak analog voltage signals are particularly susceptible to external interfer-
ence, shielded cables are generally required, and the wiring distance should be as
short as possible, not exceeding 20m, as shown in Figure 3-12. In some occasions
where the analog signal is severely interfered, a filter capacitor or a ferrite core should
be added on the analog signal source side.