-181-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-30
LED stop display
0001
~
0x1PFf
H.0043
☆
This function code sets the parameters displayed by LED when the inverter stops. When the
corresponding bit of this function code is 1, the monitoring parameter corresponding to this
bit is displayed. When multiple function codes are selected for display, they can be switched
by the keys on the operation panel.
SHIFT
7 6 5 4 3 2 1 0
Bit00: Set frequency 0001
Bit01: Bus voltage 0002
Bit02: DI input status 0004
Bit03: DO output status 0008
Bit04: AI1 voltage 0010
Bit05: AI2 voltage 0020
Bit06: PID setting value 0040
Bit07: PID feedback value 0080
15 14 13 12 11 10 9 8
Bit08: Count value
0100
Bit09: Length value
0200
Bit10: Load speed display
0400
Bit11: PLC stage
0800
Bit12: Input pulse frequency
1000
Bit13: Reserved
Bit14: Reserved
Bit15: Reserved
Figure 6-18. LED stop display corresponding map
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-31
Load speed display factor
0.001
~
655.00
1.000
☆
Through this parameter, the output frequency of the inverter and the load speed are corresp-
onded. It is used for setting when there is no high-speed pulse and the load speed needs to
be displayed, the load speed (U1-22)=P7-31*running frequency. The unit can be speed or Hz,
please set the specific parameter value according to the actual situation.
C
h
a
p
te
r
6