-183-
Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-38
Current running time set value
0.0min
~
6500.0min
0.0min
☆
When the current running timing of P7-36 is valid, and the current running time source selec-
ts 0: P7-38 setting, and the switch output selects No. 27 function, the running time of the inv-
erter reaches the set time, outputs the ON signal, and at the same time converts the freque-
ncy. The device reports that the running time has reached the fault Err39.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-39
High level timing
0.0s
~
6000.0s
2.0s
☆
P7-40
low level timing
0.0s
~
6000.0s
2.0s
☆
When the timer input terminal "on" is longer than P7-39, the output of this timer function is tu
-
rned on.
When the timer input terminal "disconnect" is longer than P7-40, the output of the timer func
-
tion is disconnected.
Fig.6-19 Schematic diagram of timer input and output operation
P7-39
P7-40
P7-39
P7-40
Timing input terminal
Timing output terminal
Function
code
Name
Description
(setting range)
Factory
Default
Change
P7-41
Activate the protection function
0
~
1
1
☆
0: Invalid (start terminal command is valid and start directly)
1: Valid
This parameter is used to improve the safety protection factor. If it is set to 1, it has two
effects:
1) The running command exists when the inverter is powered on, the running command must
be removed before the running protection state can be eliminated.
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......