Chapter 6 Description of Function Codes
Function
code
Name
Description
(setting range)
Factory
Default
Change
P1-24
The deceleration time of the
momentary stop and non-stop
deceleration stop
0.0s
~
100.0s
10.0s
★
P1-25
Instantaneous power failure and
non-stop effective voltage
60%
~
85%
80%
★
This parameter is used to judge whether the grid voltage is the threshold for instantaneous
power failure. When the bus voltage is less than P1-25, the inverter will decelerate according
to the method set by P1-23 to maintain the bus voltage constant. 100% corresponds to the
voltage level of the inverter.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P1-26
Instantaneous power failure and
non-stop recovery of voltage
85%
~
100%
90%
★
This parameter is used to judge whether the grid voltage returns to the normal threshold.
When the bus voltage is greater than P1-26, the inverter will no longer decelerate. When the
duration is greater than P1-27, the inverter will accelerate until it reaches the set frequency.
100% corresponds to the voltage level of the inverter.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P1-27
Instantaneous power failure and
non-stop recovery voltage
judgment
0.0s
~
300.0s
0.3s
★
This parameter is used for the time judgment of grid voltage recovery. When the grid voltage
is higher than P1-26, the timing starts, otherwise it is cleared to 0.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P1-28
Instantaneous stop and non-stop
automatic gain adjustment
0
~
100
40
☆
Instantaneous stop and non-stop
automatic adjustment of integral
1
~
100
20
☆
It takes effect only when P1-23=1 is selected for the instantaneous stop and non-stop mode.
It is used to adjust the deceleration speed and generally does not need to be modified.
C
h
a
p
te
r
6
-142-