Chapter 5 Function & Parameter Table
-104-
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-22
Fault
protection
action 1
0
~
22202;
Units place: Motor overload - Err14
0: Free parking
1: stop according to the stop mode
2: keep running
Ten: reserved
Hundreds place: input phase loss-Err23
Thousands place: output phase loss-Err24
Ten thousand: parameter read and write
exception - Err25
00000
☆
P9-23
Fault
protection
action 2
0
~
22222;
Ones place: Communication failure - Err27
0: Free parking
1: stop according to the stop mode
2: keep running
Tens place: External fault - Err28
Hundreds place: excessive speed deviation
fault - Err29
Thousands: User-defined fault 1-Err30
Ten thousand: user-defined fault 2-Err31
00000
☆
P9-24
Fault
protection
action 3
0
~
22022;
Ones place: PID feedback lost during
runtime - Err32
0: Free parking
1: stop according to the stop mode
2: keep running
Tens place: load loss fault - Err34
Hundreds place: software overcurrent -
Err16
Thousands place: The current continuous
running time reaches -Err39
Ten thousand: the running time reaches -
Err40
00000
☆
P9-26
Continue to
run frequency
selection in
case of failure
0: run at the current operating frequency
1: run at the set frequency
2: run at the upper limit frequency
3: Run at the lower frequency limit
4: Run at the standby frequency setting
value P9-27
1
☆
C
h
a
p
te
r
5