Chapter 6 Description of Function Codes
Hundreds: reserved
;
Thousands place: The current time of continuous operation is reached - Err39
;
Ten thousand: Cumulative running time reaches - Err40
;
Note:
When the fault protection action 1~fault protection action 3 are selected as "free stop", the
inverter will display Err** and stop directly.
When "stop by stop mode" is selected: the inverter displays Ala**, and stops by stop mode,
and displays Err** after stop.
When "continue running" is selected: the inverter continues to run and displays Ala**, and the
running frequency is set by P9-26.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-26
Continue to run frequency
selection in case of failure
0
~
4
1
☆
0: run at the current operating frequency;
1: run at the set frequency;
2: run at the upper limit frequency;
3: Run at the lower frequency limit;
4: Run at the standby frequency setting value P9-27.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-27
Abnormal standby frequency set
value
0.0%
~
100.0%
100%
☆
This value is a percentage relative to the maximum frequency, which takes effect when P9-
26 selects an abnormal backup frequency and a fault occurs.
Function
code
Name
Description
(setting range)
Factory
Default
Change
P9-28
Drop load protection option
0~1
0
☆
P9-29
Drop load detection level
0.0%
~
80.0%
20.0%
★
P9-30
Load drop detection time
0.0s
~
100.0s
5.0s
☆
When the load loss protection is enabled, that is, P9-28=1, if the output current of the inverter
is less than the load loss detection level set by P9-29 (P9-29*motor rated current), and the
C
h
a
p
te
r
6
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......