Chapter 6 Description of Function Codes
-219-
It means that the target torque is given by the maximum value of the analog quantities AI1
and AI2.
Options 1 to 6 correspond to full scale (Pd-01).
Function
code
Name
Description
(setting range)
Factory
Default
Change
PD-01
Torque digital given
-200.0%
~
200.0%
150.0%
☆
The torque setting adopts relative value, 100.0% corresponds to the rated torque of the mot-
or. The setting range is -200% to 200%, indicating that the maximum torque of the inverter is
twice the rated torque of the motor. When the motor power is greater than that of the inverter,
it will be limited to the maximum torque of the inverter.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PD-03
Torque control positive
direction maximum frequency
0.00Hz
~
Maximum
frequency (P0-14)
50.00Hz
☆
PD-04
Torque control reverse
direction maximum frequency
0.00Hz
~
Maximum
frequency (P0-14)
50.00Hz
☆
It is used to set the forward or reverse maximum running frequency of the inverter in torque
control mode.
During torque control of the inverter, if the load torque is less than the output torque of the
motor, the motor speed will continue to rise. In order to prevent accidents such as flying in the
mechanical system, the maximum speed of the motor during torque control must be limited.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PD-06
Torque command filter time
0.00s
~
10.00s
0.00s
☆
Setting this parameter value can make the torque command smoother and the control more
compliant, but the response will be slower accordingly.
Function
code
Name
Description
(setting range)
Factory
Default
Change
PD-07
Torque mode frequency
acceleration time
0.0s
~
1000.0s
10.0s
☆
C
h
a
p
te
r
6