Stop/Run parameter section:
Address
Parameter Description
0X1000/
0X9000
1000:*communication setting value (-10000
~
10000) (decimal) (unit:
0.01%), readable and writable
9000: Communication setting frequency: 0HZ
~
P0-14 (minimum unit:
0.01HZ), readable and writable
0x1001
Set frequency (unit: 0.01Hz), read only
0x1002
Running frequency (unit: 0.01Hz), read only
0x1003
Bus voltage (unit: 0.1V), read only
0x1004
Output voltage (unit: 0.1V), read only
0x1005
Output current (unit: 0.1A), read only
0x1006
Output power (unit: 0.1kW), read only
0x1007
DI input flag (unit: 1), read only
0x1008
DO output flag (unit: 1), read only
0x1009
PID setting (unit: 1), read only
0x100A
PID feedback (unit: 1), read only
0x100B
Ai1 voltage (unit: 0.01V), read only
0x100C
Ai2 voltage (unit: 0.01V), read only
0x100D
Ao1 output voltage (unit: 0.01V) read only
0x100E
PLC step (unit: 1), read only
0x100F
Speed (unit: 1rpm), read only
0x1010
Count value input (unit: 1), read only
0x1011
Input pulse frequency (unit: 0.01kHz), read only
0x1012
Feedback speed (unit: 0.1Hz), read only
0x1013
Remaining running time (unit: 0.1min), read only
0x1014
AI1 voltage before calibration (unit: 0.001V), read only
0x1015
AI2 voltage before calibration (unit: 0.001V), read only
0x1016
Actual linear speed (unit: 1m/min), read only
0x1017
Load speed (unit: user-defined, refer to P7-31), read only
0x1018
Current power-on time (unit: 1min), read only
0x1019
Current running time (unit: 0.1min) read only
0x101A
Input pulse frequency (unit: 1Hz), read only
C
h
a
p
te
r
1
0
Summary of Contents for 2S-0.4G-B
Page 6: ...Safety and Attentions Chapter 1 1 1 Safety Matters 6 1 2 Use Considerations 9...
Page 80: ...Function Parameter Table 5 1 Functional group 78 Chapter 5...
Page 126: ...Function Parameter Table Chapter 6...
Page 245: ......
Page 249: ......
Page 255: ......